3.2.7 AIF-100/CO Contact Output Control Interface
The CCU sends all contact output control data for AIF-100/CO auxiliary
control devices (address 2-250) out the RS-485 output channels 4 and 6.
The AIF-100/CO units are addressable like the FastScan/SmartScan
assemblies. Address 1 cannot be used for AIF-100/CO units. Address 1
is reserved for the optional MX-4248 I/O Board for the HD video switcher.
Manual control of the contact outputs is performed by an operator at a JPD-
100 Joystick Controller. The address of the AIF-100/CO is called up on the
JPD-100 as the primary control camera. Refer to the JPD-100 Operator’s
Manual.
Automatic operation of the contact outputs occurs if auxiliary control
commands are stored in a MultiCall and the MultiCall is started. Refer to
programming MultiCalls in Section 4 of this manual.
3.2.8 Host Computer Interface
The CCU has an RS232 simplex input port (COM1) for a host computer
interface. The host computer can send commands to the CCU to perform
the following functions:
Video Switcher Call
Send A SmartScan Unit to a PreShot
Activate an Alarm
When the CCU receives an activate alarm command from the host
computer, the CCU activates the MultiCall assigned to the alarm point.